|  | ESD5200 The speed control unit is rugged enough to be placed in a  control cabinet or engine mounted enclosure with other dedicated control  equipment. If water, mist, or condensation may come in contact with the  controller, it should be mounted vertically. This will allow the fluid to drain  away from the speed control unit. Extreme heat should be avoided. Magnetic  speed sensor wires connected to Terminals C and D MUST BE TWISTED AND/OR  SHIELDED for their entire length. The speed sensor cable shield should ideally  be connected as shown in Diagram 2. The shield should be insulated to insure no  other part of it comes in contact with engine ground, otherwise stray speed  signals may be introduced into the speed control unit. With the engine stopped,  adjust the gap between the magnetic speed sensor and the ring gear teeth. The  gap should not be any smaller than 0.020 in. (0.45 mm). Usually, backing out  the speed sensor 3/4 turn after touching the ring gear teeth will achieve a  satisfactory air gap. The magnetic speed sensor voltage should be at least 1V  AC RMS during cranking.Simple and effective remote  variable speed can be obtained with the ESD5200 Series speed control unit. A  single remote speed adjustment potentiometer can be used to adjust the engine  speed continuously over a specific speed range. Select the desired speed range  and corresponding potentiometer value. (Refer to TABLE 1.) If the exact range  cannot be found, select the next higher range potentiometer. An additional  fixed resistor may be placed across the potentiometer to obtain the exact  desired range. Connect the speed range potentiometer as shown in Diagram 1. To  maintain engine stability at the minimum speed setting, a small amount of droop  can be added using the DROOP adjustment. At the maximum speed setting the  governor performance will be near isochronous, regardless of the droop  adjustment setting. |