|  | Deep Sea Electronics PLC The Model 501K-1 is a Manual  Engine Control Module, which has been designed to manually control the engine  via a key switch on t front panel.The  module is used to start and stop the engine, indicating fault conditions;  automatically shutting down the engine and indicating the engine failure by LED  giving true first up fault annunciation. Operation of the module is via a three  position key switch mounted on the front panel with STOP(O), RUN(I) and START(II)positions.In the¡®O¡¯position the DC supply is removed from the module and the run  relay and alarm output are de-energised.If the switch is turned to the¡®I¡¯position the module is powered up and  the run relay is energised, activating the engine fuel/ignition system and the  protection hold-off timer is initiated.If the switch is moved to the¡®II position and held against the spring  return, a positive supply is applied to the relevant output terminal and on to  the starter motor.Once the engine has  started the switch should be released and allowed to return to the¡®I¡¯position. Operation of any of the following alarms; Low Oil Pressure, High  Engine Temperature, Auxiliary Shutdown, Overspeed (Optional), will cause  the run relay to de-energise.This will  remove the fuel/ignition supply from the engine and bring it to rest.The alarm output will be activated giving a  positive DC output. Each alarm channel has it¡¯s own LED indicator and once  activated no further alarm conditions will be accepted.The alarm output and relevant LED will  remain active until the unit is reset by turning the switch to the¡®O position.Dimensions: 72 X 72 X 118.5 (Excluding Key-switch) 
 |